Fans Article ABL-XFRCU
Roof fan ABL-XFRCU
Roof axial exhaust fanABL-XFRCU(upblast) – exhaust from the room directly through the roof, without ventilation chambers and space for equipment inside the…
Calculated after specifying the performance, execution and composition of the supply.
Send us the parameters or technical specifications - the engineer will specify the equipment for your facility.
- Air consumption
- 5,000 m³/h
- Pressure
- 250 Pa
- Power
- 3 kW
- Type
- Roof axial discharge (upblast)
Engineering solution
What this equipment is designed to solve
Roof axial exhaust fanABL-XFRCU(upblast) – exhaust from the room directly through the roof, without ventilation chambers and space for equipment inside the building. Solid aluminum alloy body, stamped impeller with G4.0 balancing, laser cutting parts.
The fan is designed for year-round outdoor operation. The emission is directed upward – polluted air and odors move away from the roof rather than spreading across it. Operating temperature up to160 °C allows XFRCU to be used on commercial kitchen hoods and hoods; in some cases – like a smoke fan.
Maintenance is simple: the lid is opened by hand, allowing access to the wheel and motor for cleaning. Power 0.18–3.0 kW, pressure ≈155–250 Pa, performance according to standard size. Mounting sleeve, roof penetration and piping are produced by ABL in Temirtau.
Application
Suitable applications
- Commercial kitchens, food courts, exhaust hoods
- Warehouses and logistics complexes
- Supermarkets and shopping centers
- Production premises
- Sports facilities
- Greenhouses
Preliminary parameters
Characteristics
Values are not contractual until the selected configuration is confirmed in the technical proposal and data sheet.
| Type | Roof axial discharge (upblast) |
|---|---|
| Housing | Solid aluminum alloy, laser cut |
| Pressure | ≈155 – 250 Pa |
| Engine power | 0.18 – 3.0 kW |
| Air consumption | By standard size - selection by operating point |
| Ambient temperature | Up to 160 °C (can work as a smoke fan) |
| Wheel balancing | G4.0 |
| Service | Hand-opening lid for access to wheel and engine |
| Execution | Outdoor, year-round use on the roof |
The posted review of industrial fans does not confirm the designation of this model; operating point, engine, temperature, noise and dimensions are confirmed by the passport of the selected version.
For procurement and approval
Documentation
Frequently Asked Questions
Vertical exhaust removes polluted air from the roof: grease from kitchen hoods and odors do not settle on the roofing and are not drawn back into the air supply systems and windows. For kitchen hoods this is a key requirement.
Yes, XFRCU is designed for year-round outdoor use: the solid aluminum alloy body is resistant to precipitation and temperature changes. ABL manufactures the mounting sleeve and roof penetration for a specific roof.
The cover can be opened by hand without tools to provide access to the impeller and motor for inspection and cleaning. For kitchen hoods, periodic cleaning of grease is the main maintenance procedure.
Do you need to select equipment for your project?
Send the terms of reference, questionnaire or basic parameters. We will prepare a complete set and a commercial offer.